Modularity offers users of air dryers a number of advantages. Depending on the process or process changes, the respective modules can be tailored to the specific application.

ULT does not supply off-the-shelf systems, but offers users individual solutions for ideal process air drying, because no application is the same as another.

Based on standard modules, we select the right solution for you - for process rooms of different sizes and framework conditions.

 

Sorption modules ULT Dry-Tec - available in different performance classes

modules ult dry-tec various performance classes

 

Modular concept ULT Dry-Tec

ult drytec modular concept with cooling modules
 

Left: ULT Cool -Tec V (module for pre-cooling)

Center: ULT Dry-Tec (sorption module)

Right: ULT Cool-Tec N (module for after-cooling)

Modules also available individually

 

ULT Dry-Tec 3.x arid

ult dry tec module 3.1 arid

 

Process air (inlet / outlet) 
Process volume flow inlet nom. 350 m³/h
Process volume flow outlet process-dependent
Process air fan power 360 W
Total pressure loss over the entire module system approx. 500 Pa (with fully loaded filter)
Free available pressure of the process air min. 1,000 Pa
Dimensions (WxHxD) 1,050x760x580 mm
Operating mode process / system continuous operation
Regeneration air (inlet / outlet) 
Regeneration air volume flow 100 m³/h

Outlet regeneration air,

loaded with water molecules

process-dependent
Freely available external pressure at the outlet min. 800 Pa for ducts outlet air, loaded
Regeneration air fan power 70 W (EC fan, infinitely variable)
Supplied power for electr. heating register max. 1.9 kW

 

ULT Dry-Tec 7.x arid

ult dry tec module 7.2 arid

 

Process air (inlet / outlet) 
Process volume flow inlet nom. 750 m³/h
Process volume flow outlet process-dependent
Process air fan power 0.7 kW
Total pressure loss over the entire module system approx. 800 Pa (with fully loaded filter)
Free available pressure of the process air min. 1,200 Pa
Dimensions (WxHxD) 830x1,400x820 mm
Operating mode process / system continuous operation
Regeneration air (inlet / outlet) 
Regeneration air volume flow 300 m³/h

Outlet regeneration air,

loaded with water molecules

process-dependent
Freely available external pressure at the outlet min. 1,500 Pa for ducts outlet air, loaded
Regeneration air fan power 0.36 kW (EC fan, infinitely variable)
Supplied power for electr. heating register max. 6 kW

 

ULT Dry-Tec 13.x arid

ult dry tec module 13.x arid

 

Process air (inlet / outlet) 
Process volume flow inlet nom. 1,300 m³/h
Process volume flow outlet process-dependent
Process air fan power 4.5 kW
Total pressure loss over the entire module system approx. 800 Pa (with fully loaded filter)
Free available pressure of the process air min. 200 Pa
Dimensions (WxHxD) 1,124x1,640x820 mm
Operating mode process / system continuous operation
Regeneration air (inlet / outlet) 
Regeneration air volume flow 450 m³/h

Outlet regeneration air,

loaded with water molecules

process-dependent
Freely available external pressure at the outlet min. 1,000 Pa for ducts outlet air, loaded
Regeneration air fan power 0.75 kW (EC fan, infinitely variable)
Supplied power for electr. heating register max. 15 kW

 

ULT Dry-Tec 25.x arid

ult dry tec module 25.x arid
 

Process air (inlet / outlet) 
Process volume flow inlet nom. 2,500 m³/h
Process volume flow outlet process-dependent
Process air fan power 6 kW
Total pressure loss over the entire module system approx. 1,500 Pa (with fully loaded filter)
Free available pressure of the process air min. 1,200 Pa
Dimensions (WxHxD) 1,420x1,640x820 mm
Operating mode process / system continuous operation
Regeneration air (inlet / outlet) 
Regeneration air volume flow 750 m³/h

Outlet regeneration air,

loaded with water molecules

process-dependent
Freely available external pressure at the outlet min. 1,000 Pa for ducts outlet air, loaded
Regeneration air fan power 0.75 kW (EC fan, infinitely variable)
Supplied power for electr. heating register max. 22 kW

 

ULT Dry-Tec 50.x arid

ult drytec 50.x arid

 

Process air (inlet / outlet) 
Process volume flow inlet nom. 5,000 m³/h
Process volume flow outlet process-dependent
Process air fan power 7.5 kW
Total pressure loss over the entire module system approx. 1,000 Pa (with fully loaded filter)
Free available pressure of the process air min. 3,000 Pa
Dimensions (WxHxD) 1,740x1,830x1,070 mm
Operating mode process / system continuous operation
Regeneration air (inlet / outlet) 
Regeneration air volume flow 1,670 m³/h

Outlet regeneration air,

loaded with water molecules

process-dependent
Freely available external pressure at the outlet min. 800 Pa for ducts outlet air, loaded
Regeneration air fan power 2.3 kW (EC fan, infinitely variable)
Supplied power for electr. heating register max. 2 X 32.5 kW

 

ULT Dry-Tec 50.x arid

ult dry tec 50.xx arid

 

Process air (inlet / outlet) 
Process volume flow inlet nom. 7,500 m³/h
Process volume flow outlet process-dependent
Process air fan power 7.5 kW
Total pressure loss over the entire module system approx. 1,000 Pa (with fully loaded filter)
Free available pressure of the process air min. 2,000 Pa
Dimensions (WxHxD) 2,130x2,500x1,240 mm
Operating mode process / system continuous operation
Regeneration air (inlet / outlet) 
Regeneration air volume flow 2,570 m³/h

Outlet regeneration air,

loaded with water molecules

process-dependent
Freely available external pressure at the outlet min. 1,800 Pa for ducts outlet air, loaded
Regeneration air fan power 4 kW (EC fan, infinitely variable)
Supplied power for electr. heating register max. 2 X 27.5 kW

 

ULT Cool-Tec 3-75 V/N

ult cool tec pre-cooler and after-cooler
 
 ult cool tec pre-cooler after-cooler
 
  • All cooling modules can be used as pre- or after-coolers
  • Standard cooling capacity range between 2.5 kW and 120 kW
  • In addition to standard variants, specially manufactured designs are possible for all sizes and applications

 

Do you have any questions about our modules or would you like to know which sorption module is suitable for your specific application? Just contact us. We look forward to your message.

eMail 0351 320480-0

Contact request ULT AG

Please enter the name of your company.
Please enter your name.
Please enter your address.
Please enter your ZIP code and location.
Please enter the country.
Please enter your phone number.
Bitte geben Sie Ihre Faxnummer ein.
Please enter your e-mail address.
Ungültige Eingabe.
Ungültige Eingabe.
Ungültige Eingabe.
Ungültige Eingabe
Ungültige Eingabe
Bitte geben Sie die Anzahl der Absaugstellen, an denen gleichzeitig gearbeitet wird, ein.
Bitte geben Sie an, welches Material Sie verarbeiten.
Bitte geben Sie an, welches Bearbeitungsverfahren Sie anwenden.
Please accept our GTC.
Please accept our data protection guidelines.
Ungültige Eingabe